D10024
D10024 Operator’s Guide
Copyright © 2001 Radionics Page 21 46521C
Control Level 3
5.0 Control Level 3 (Programmer Functions)
Note: Commission, configure, networking and certain disable options are not available to Control Level 2 operators. These
options are reserved for Control Level 3 operators. See the Analog Fire Alarm Control Panels Programming Guide
(P/N: 46482) for complete information on commissioning and programming the D10024 Analog FACP.
5.1 Enable/Disable Sounders (NAC Devices)
All sounders (NAC devices such as horns, bells, strobes, etc.) and relays can be enabled or disabled from the control
panel during testing. Disabling NAC devices requires a Control Level 3 passcode. No passcode is required to enable
NAC devices.
From the Main Menu, press [5] for Disable. The Disable Menu is displayed.
Press [5] for Outputs. The display shows:
1) Sounders 2) Relays
ENABLED ENABLED
Figure 19: Outputs Submenu
Press 1) Sounders. The display prompts for the Control Level 3 passcode. Enter the passcode. The panel buzzer will
sound, the System Trouble LED will light and the display message will indicate that the output is disabled.
Press the [Trouble Silence] key to silence the buzzer. The Trouble Silenced LED will light.
The disabled output must be enabled before the system can be reset.
To enable the outputs, press the [No] key to revert to the Main Menu.
Press the [4] key to enter the Enable Menu.
Press [5] for Outputs.
Press [1] for Sounders. The system will reset and the Trouble Silenced LEDs will go out.